Measurement of Highway-Related Noise

Appendix A
Relative Humidity Computation

This appendix presents the procedures for converting measured dry and wet bulb temperatures into relative humidity expressed in percent.

  1. Convert Dry Bulb temperature from °F to °C:

    Dry, °C =[(Dry,°F) -32] /1.8

  2. Convert Dry Bulb temperature from °C to °K:

    Dry, °K = (Dry, °C) + 273.15

  3. Repeat steps 1 and 2 to convert Wet Bulb temperature (Wet) to °K.

  4. Compute the Saturation Pressure, assuming standard-day ambient atmosphere pressure, for the Dry Bulb temperature (DrySatPres):

    DrySatPres = e19.163 - (4063.2 + 184089.0/Dry)/Dry

  5. Repeat step 4 to compute the Saturation Pressure for the Wet Bulb temperature (WetSatPres).

  6. Compute the Relative Humidity (RH) in percent:

    RH, % = 100 × [WetSatPres/DrySatPres]