U.S. Department of Transportation
Federal Highway Administration
1200 New Jersey Avenue, SE
Washington, DC 20590
202-366-4000


Skip to content
Facebook iconYouTube iconTwitter iconFlickr iconLinkedInInstagram

Federal Highway Administration Research and Technology
Coordinating, Developing, and Delivering Highway Transportation Innovations

 
REPORT
This report is an archived publication and may contain dated technical, contact, and link information
Back to Publication List        
Publication Number:  FHWA-HRT-14-023    Date:  May 2014
Publication Number: FHWA-HRT-14-023
Date: May 2014

 

Federal Highway Administration Design Manual: Deep Mixing for Embankment and Foundation Support

CHAPTER 6: ANALYSIS OF WIRE CONDITIONS

GENERAL OVERVIEW

Once the wrapping was removed, a general inspection of the cable was performed. It appeared that the cable was heavily covered by a white powder, which was a mix of salt residue and zinc oxide. In a couple of spots along the length of the cable, small pockets of water were found on the side portion of the cable cross section. Heavy corrosion appeared at the location where the sensors' wires exited the cable. Apparently, the neoprene strap that served as a protection for the electric wires functioned as a moisture trap and kept the wires in a wet environment for a long time. In addition, areas of high ferrous corrosion occurring underneath the stainless steel straps were easily identifiable in the south part of the cable, as shown figure 123, whereas the north side of the cable seemed to have experienced little to no ferrous corrosion (see figure 121).

CORROSION UNDER NEOPRENE PROTECTIVE STRAP

Upon removal of the neoprene strap, it was found that large amounts of what appeared to be uniform corrosion occurred under the neoprene wrapping. Furthermore, the strap was still moist when removed from the cable surface. The area where the neoprene strap was is shown in figure 126. Figure 130 and figure 131 show progressively closer views of the corroded area. It is interesting to note that the highest density of corrosion appears to have occurred on the top side of the cable directly in line with the water and heat sources.

This photo shows the corroded portion of the cable surface under the neoprene wrapping. The center of the intact cable is shown with all aluminum and neoprene wrapping removed. The surface wires are shown with stage 2 to stage 4 levels of corrosion. The worst corrosion is located at the top of the cable. The sensor wiring is seen exiting the cable slightly to the right of the main corroded area.
Figure 130. Photo. Corroded area under neoprene wrapping

This photo shows a close-up view of the corroded portion of the cable surface under the neoprene wrapping. The general area of stage 4 corrosion located on the top of the cable is highlighted.
Figure 131. Photo. Close-up view of corroded area under neoprene wrapping

A close-up investigation of the top of the cable revealed stage 4 uniform corrosion for the wires on the outer layers in which close to 90 percent of the high-strength steel wires had undergone ferrous corrosion (see figure 132 and figure 133). This area was the one most exposed to higher temperatures (directly below the central heating lamp) and rain. The presence of the neoprene strap helped maintain high levels of humidity that, with high temperature levels, created ideal conditions for the progress of corrosion.

This photo shows wires with stage 4 corrosion on the top of the cable surface. A 6-inch (152.4-mm) area with approximately 20 wires with stage 4 corrosion is highlighted.
Figure 132. Photo. Wires with stage 4 corrosion on the top of the cable surface

This photo shows a close-up view of the corroded wire from figure 132. An individual wire with severe ferrous corrosion and corrosion product is visible.
Figure 133. Photo. Close-up view of corroded wire

STAINLESS STEEL STRAPS

Galvanic as well as crevice and pitting corrosion in areas of moisture build-up occurred in this cable. The build-up of salt and/or zinc oxide as well as ferrous oxide below the stainless straps was easily identifiable, as shown in figure 122 and figure 123. These straps were made of unknown chemical composition, so they may have facilitated the onset of corrosion at their location. In addition, the small gaps between the strap and the outer wires ended up trapping rain water and moisture for a long time, initiating crevice and pitting corrosion. The corrosion of the wires under the stainless steel straps tended to increase toward the south side of the cable. As previously mentioned, the cable was constructed on a slight angle for drainage purposes, thus the increase of ferrous oxide was directly a result of the increased moisture content at the south side of the cable. Mild salt build-up, zinc oxide, and ferrous oxide may be seen under the stainless steel straps, as shown in figure 134.

This photo shows the formation of salt deposit and zinc/ferrous corrosion products on the surface of wires next to a stainless steel strap. Salt deposits built up around the location of steel straps with ferrous corrosion forming at the contact point of the edge of a stainless steel strap and the cable wires.
Figure 134. Photo. Salt build-up and zinc/ferrous corrosion product

At points closer to the south side of the cable, more critical forms of corrosion formed. The presence of high moisture, the potential difference between the stainless steel of the strap and the zinc-coated high-strength steel wires, and the presence of crevices created by the voids between the straps and the wires initiated heavy pitting corrosion (see figure 135 and figure 136). From this result, it is noteworthy that the use of stainless steel straps, which are commonly used in practice, should be carefully considered in environments with aggressive conditions.

This photo shows pitting corrosion under the stainless steel strap. The salt deposit was cleaned from the wire surface to reveal pitting corrosion. Ferrous oxide is seen at points where the straps contacted the cable wires.
Figure 135. Photo. Pitting corrosion under stainless steel strap

This photo shows a close-up view of wires with localized corrosion under the stainless steel strap. The surface of the wire is visibly uneven as black pits break up the wire surface which is covered in white zinc oxide.
Figure 136. Photo. Close-up view of pit

CABLE BANDS

The cable bands on either end of the cable mockup specimen presented another place for moisture entrapment. Similar to the stainless steel straps, the corrosion of the high-strength steel wires was greater at the south side of the cable. Looking eastward at the north side of the cable, it is possible to identify what may be assumed to be stage 2 corrosion (near complete zinc oxidation) and definite signs of stage 3 corrosion (ferrous corrosion is identifiable at approximately 20 to 30 percent coverage) (see figure 137 and figure 138).

This photo shows the north end of the cable without the upper part of the cable band. The top portion of the loading end’s cable band has been removed. Stage 2 and stage 3 corrosion are shown on the wires from the surface of the cable. The loose wires are kept in place with duct tape.
Figure 137. Photo. North end of cable with band removed

This photo shows wires under the cable band showing sign of stage 3 corrosion. A close-up of an area of approximately 3 by 3 inches (76.2 by 76.2 mm) highlights white zinc and rust colored ferrous corrosion product.
Figure 138. Photo. Wires at north end of cable with stage 3 corrosion

The corrosion under the cable band at the south end of the cable was more severe than that at the north end, as both the percentage of area covered by stage 3 corrosion (see figure 139), and the degree/depth of corrosion was greater at the south end (see figure 140).

This photo shows the south end of the cable without the upper part of the cable band. The top portion of the jacking end’s cable band has been removed. Stage 2 and stage 3 corrosion are shown on the wires from the surface of the cable. Duct tape used to keep the free wires in place during construction is shown to be extremely worn. Stage 3 ferrous corrosion is more prevalent closer to the end of the cable.
Figure 139. Photo. South end of cable with band removed

This photo shows wires under the cable band showing signs of stage 3 corrosion. A 2-by-2-inch (50.8-by-50.8-mm) area on the top of the south end of the cable displays a large amount of ferrous corrosion.
Figure 140. Photo. Wires at south end of cable with large percentage of stage 3 corrosion

The corrosion at the south end cable band was most heavily concentrated to the left portion of the outer surface. This was the result of an irregular (uncontrollable) path of water penetration. The ferrous oxide was found where the cable band began, suggesting an interaction between the galvanized wires, the steel cable band, and the surrounding environment.

The cable bands themselves also experienced significant amounts of corrosion. A high concentration of ferrous corrosion product was found on the cable band at the location where the cable band began on the south side of the cable. On the surface, the greatest amount of corrosion was seen on the teeth where the top and bottom cable bands met, which is an area directly in contact with air (see figure 141).

This photo shows the south end of cable highlighting the teeth of the cable band. The jacked end of the cable is highlighted. The bolts have been removed from the cable band. The band sits around the cable with the teeth of the top and the bottom separated by approximately 5 inches (127 mm). Stage 2 and stage 3 corrosion is seen between the teeth of the cable bands.
Figure 141. Photo. South end of cable highlighting teeth of cable band

On the underside of the cable band, a substantial amount of salt and/or zinc oxide and ferrous oxide was found (see figure 142). The concentration of ferrous corrosion was observed on the left side of the cable band.

This photo shows the interior of a cable band with salt deposits as well as zinc and ferrous corrosion products. The corrosion product reflects the patterns of the individual wires.
Figure 142. Photo. Interior of top of south side of cable band

Underside Openings

Midway through the test program at points approximately 3.94 ft (1.2 m) from either end of the cable mockup, four holes were placed in the cable wrapping (see figure 143). Two 11.89-by-11.89-inch (30.5-by-30.5-cm) openings were made in the underside of the wrapping and at a location on the topside of the cable, and two 0.99-by-0.99-inch (2.54-by-2.54-cm) openings were made 3.94 ft (1.2 m) from the jacking end to facilitate the influx of moisture to the inside of the cable mockup and accelerate corrosion of the wires (see figure 144).

This photo shows a mockup cable specimen within an environmental chamber. Green circles are present to highlight the location of two holes placed in the aluminum cable cover. The holes are located on the bottom side of the cable. The total cable and the loading frame are shown with the jacking ends to the right side of the image.
Figure 143. Photo. Mockup cable specimen within environmental chamber and location of
both holes

This photo shows a close-up view of one of the 11.89-by-11.89-inch (30.5-by-30.5-cm) holes placed in the aluminum cable cover. The individual wires of the bottom of the cable mockup are shown. Salt deposit and stage 1 zinc corrosion product can be seen on the wires.
Figure 144. Photo. Image of one of the 11.89-by-11.89-inch (30.5-by-30.5-cm) holes
placed in the aluminum cable cover

During cable disassembly, the area highlighted in figure 144 was analyzed and documented. A solid white coating developed and enveloped the exposed wires (see figure 145 and figure 146). It is evident that ferrous corrosion was not present; the wires were covered by a thick layer of a white substance mainly composed of salt but also with the presence of zinc oxide (see figure 146). The presence of such a high concentration of salt in the test solution was justified by the fact that test conditions were supposed to create harsh conditions for the sensor system.

This photo shows a close-up view of product that formed where the 11.89-by-11.89-inch (30.5-by-30.5-cm) hole was placed in the aluminum cable cover. The aluminum cover has been removed. The square area that was openly exposed to the chamber environment is completely covered in an off-white product. The wires that were covered by the aluminum wrapping are grey with traces of white product covering them.
Figure 145. Photo. Product that formed where the 11.89-by-11.89-inch (30.5-by-30.5-cm)
hole was placed in the aluminum cable cover

This photo shows a close-up view of an area of approximately 2 by 2 inches (50.8 by 50.8 mm) with the wires in the opening covered by a thick layer of a white substance, mainly composed of salt but also with the presence of zinc oxide.
Figure 146. Photo. Close-up view of the product formed on the high-strength steel wires

INTERIOR OF CABLE

With respect to the inner strands, the general observations were as follows:

The interior of the cable showed areas where heavy salt deposition occurred. These areas showed no particular pattern, following more the potential path of the water that penetrated inside the wrapping. Such areas were more frequent in the south end of the cable because of the specimen inclination. In addition to these areas of salt deposition, it appeared that extensive zinc coating corrosion occurred. Almost the totality of the inside wires were coated with a white dust, and once this dust was removed, the wires had a non-shiny zinc surface. Figure 147 shows the inner core of the specimen.

This photo shows the inner core of the specimen during disassembly. The image is taken at the longitudinal center of the mockup specimen. A large amount of white product (salt and zinc oxide) can be seen. The reinforced tape that was placed on all strands can be seen to be broken on the long tensioned strands. The cable mockup is shown during an intermediate phase of the deconstruction.
Figure 147. Photo. Inner core of the specimen during disassembly

INTERNAL CABLE STRAPS

Areas that were highly subjected to corrosion activity were those located adjacent to the nylon straps embedded within the cable (see figure 148). These straps were placed only at one location along the length of the cable to protect the electrical wires from the sensors during compaction operations. The gaps next to the straps were not sealed before the wrapping, with the intention that water could easily penetrate the interior of the cable to activate the sensors. In real-life applications, it is strongly recommended to seal these openings to avoid water penetration inside the cable.

This photo shows an orange nylon strap embedded within the cable near the sensor locations. The straps are approximately 1.5 inches (38.1 mm) wide and used to protect the sensors from the compaction forces applied to the cable. A small bit of stage 3 corrosion can be seen on one of the strands in the image.
Figure 148. Photo. Orange nylon strap embedded within cable

Basically, these straps acted similarly to the neoprene wrapping. That is to say, the nylon straps held any moisture present within the cable for extended periods of time, keeping the solution necessary for the electrochemical corrosion reaction. The corrosion product formed in the distinct shape of the overlapping strap (see figure 149).

This photo shows a strand placed on a stand for analysis. Mild stage 3 corrosion is seen on the left side of the strand, while more severe stage 3 corrosion can be seen on the right side. The corroded area is the same width as the orange nylon straps. The corroded area exists at a location where the strap was present.
Figure 149. Photo. Corrosion formation at nylon strip location

As was seen with the corrosion associated with the neoprene wrapping, the corrosion around the nylon straps was fairly uniform. Heavy stage 4 corrosion was seen on the bottom of a strand in contact with a nylon strap (see figure 150).

This photo shows a close-up view of the corroded area from the previously mentioned strand. The corroded wires actually show some areas of stage 4 corrosion.
Figure 150. Photo. Close-up view of the wires with stage 4 corrosion

PRE-CORRODED STRANDS

New strands within the cable mockup specimen that were adjacent to the two pre-corroded strands also experienced heavy amounts of corrosion on the contact surface between the strands. As was commonplace with the other corrosion documented, corrosion of strands adjacent to pre-corroded strands was heaviest in the central and southern sections of the cable due to the slight inclination of the cable specimen toward the jacking end. Following the nomenclature introduced in figure 116, strands 8R and 9R were pre-corroded with the intent of generating some hidden corrosion damage for the direct sensing technologies. Looking at the surface of strand 16R in contact with strand 9R, it was evident the presence of ferrous corrosion in stage 3, approaching stage 4, was seen in the area adjacent to strand 9R even on the north side of strand 16R (see figure 151). In fact, several sections displayed stage 4 corrosion and black oxides (see figure 152).

This photo shows the north side of cable pre-corroded strand and adjacent side of a separate strand. The 1-ft (0.30-m) area of the adjacent strand highlights the onset of corrosion resulting from the contact with the pre-corroded strand.
Figure 151. Photo. North end of cable—pre-corroded strand 9R (bottom) and adjacent side
of strand 16R

This photo shows a close-up view of the strand adjacent to the pre-corroded strand. The adjacent side with an area of approximately 2.5 by 2.5 inches (63.5 by 63.5 mm) shows stage 3 corrosion.
Figure 152. Photo. North end of cable close-up of 16R showing stage 3 corrosion

The effect of the contact between the corroded strand and the initially uncorroded strand was evident. Even greater amounts of ferrous corrosion were seen on the southern end of strand 16R (see figure 153). At the southern end, nearly the entire adjacent face had undergone stage 4 corrosion (see figure 154 and figure 155). Once again, it appears that the slight angle at which the cable sat caused a greater amount of moisture build-up in the southern end of the cable; however, unlike the corrosion under the stainless steel straps, the extent of the corrosion caused by the pre-corroded strands did not differ drastically from one end to the next. The corroded surface of the pre-corroded strand provided more surface area for water particles to adhere to, thereby increasing the time of wetness of the material, the time of wetness on the adjacent strand face, and the length of the corrosive electrochemical reaction.

This photo shows the south side of the cable’s pre-corroded strand and the adjacent side of a separate strand. The 1-ft (0.305-m) area of the adjacent strand highlights a significant amount of corrosion resulting from the contact with the pre-corroded strand.
Figure 153. Photo. South end of cable pre-corroded strand 9R (bottom)

This photo shows a close-up view of the strand adjacent to the pre-corroded strand on the cable’s south side. The area displays stage 4 corrosion.
Figure 154. Photo. South end of cable adjacent side of strand 16R

This photo shows a close-up view of the wires in the strand mentioned in the previous figure. Ferrous oxide and rust product can be seen.
Figure 155. Photo. South end of cable close-up of 16R showing stage 4 corrosion

 

Federal Highway Administration | 1200 New Jersey Avenue, SE | Washington, DC 20590 | 202-366-4000
Turner-Fairbank Highway Research Center | 6300 Georgetown Pike | McLean, VA | 22101